VIBRATIONS TRANSMITTER mod. Ex TR-26
Function
The integrated transmitter mod. Ex TR-26 measures the Absolute Vibrations of any rotating
machine support and is able to interface itself directly (two-wires technique, current loop 4 to 20
mA) with an acquisition system (PLC or DCS).
The transmitter reduces at maximum installation and wiring incidence, that normally limits the
possibilities to apply the traditional systems for vibration monitoring.
The transmitter is certified for applications in areas classified as:
- Ex II 2 G Ex ia IIC T6 or T5 or T4
General description
The transmitter, assembled through direct fastening on the machinery, generates a current signal (4
to 20 mA) that is proportional respectively to vibration speed or acceleration.
The transmitter is composed of a stainless steel body having a threaded machine connection; the
connection with the users is performed by means of a MIL-C-5015 connector (2 poles), included.
NOTE: The transmitter is available in different configurations and becomes operative only after its
correct electrical connection, as per drawing no. 85465-P; it doesn’t need setup or maintenance.
Technical characteristics
Vue de la page 0
1 2 3 4 5 6 7

Résumé du contenu

Page 1 - Ex TR-26

----------------------------------------------------------------------------------------------------------------------VIBRATIONS TRANSMITTER mod. Ex T

Page 2

2Composition Integrated transmitter body, in AISI 316L stainless steel material.Power supply 24 Vdc (10 to 35 Vdc) current loop 4 to 20 mA (two-wire

Page 3 - Maximum load [Ohm]

3Figure 2 – Maximum allowable load on current loop01002003004005006007008009000 5 10 15 20 25 30 35Power supply [V]Maximum load [Ohm]

Page 4

4ASSEMBLYN.B.: the operations must be performed, if possible, when the machine is OFF and by using themaximum delicateness in order to avoid any trans

Page 5 - 0722 II 2 G Ex ia IIC T6

5Notes for identification:The transmitter is constructed to be correctly used, according to the conditions set out by thefollowing table:Certification

Page 6 - Ordering example

6Ordering dataA B CTR – 26 /  /  / where,A : measuring field0 0 to 10 mm/s RMS1 0 to 20 mm/s RMS2 0 to 50 mm/s RMS3 0 to 100 mm/s RMS4 0 to 1 g RMS

Page 7 - Ex TR-26 05 gb

7Ex TR-26 05 gbASTM09120